Suzhou Electric Appliance Research Institute
期刊号: CN32-1800/TM| ISSN1007-3175

SUBSCRIPTION MANAGEMENT

发行征订

首页 >> 发行征订 >> 征订方式

基于场路耦合的超高压GIS母线温度场研究

来源:电工电气发布时间:2022-08-29 13:29浏览次数:500

基于场路耦合的超高压GIS母线温度场研究

王振芹,孙桂林,张永刚,陈连业
(传奇电气(沈阳)有限公司,辽宁 沈阳 110136)
 
    摘 要:超高压 GIS 母线发热的最高点主要出现在触头、触指部位。运用有限元方法,建立了带有触头、触指的 550 kV GIS 母线三维电磁场-流场-温度场耦合有限元求解模型。将触指进行合理简化,计算了母线导体、触头、触指等各部位元件的功率损耗,并将其作为发热源,耦合至流场-温度场求解模型,计算出母线温度场分布。将计算结果与温升试验数据对比,触头温度误差在0.3%,导体温度误差在1.04%,外壳温度误差在4%,证明了触指简化模型的合理性与正确性,对 GIS 母线设计以及触头、触指的温度场仿真具有指导意义。
    关键词: 触头;触指;GIS 母线;耦合场;接触电阻;温度场
    中图分类号:TM595     文献标识码:A     文章编号:1007-3175(2022)08-0031-05
 
Research on Temperature Field of EHV GIS Bus
Based on Field-Circuit Coupling
 
WANG Zhen-qin, SUN Gui-lin, ZHANG Yong-gang, CHEN Lian-ye
(Trench High Voltage Product Ltd, Shenyang 110136, China)
 
    Abstract: The highest heating point of the EHV GIS bus often occurs in contacts and contact fingers. This paper used the finite element method to establish a coupled finite element solution model of the magnetic field, flow field, and temperature field of the 550 kV GIS bus with contacts and contact fingers. This research simplified the contact finger and calculated the power dissipation of components from different parts, such as bus conductor, contact, and finger contact. It took the contact finger as a heat source, coupled to flow field and temperature field solving model, furthermore figure out the bus temperature field distribution. In addition, it compared the calculation results to the data of the temperature rise test. The contact temperature error was 0.3%, the conductor temperature error was 1.04%, and the outside temperature error was 4%. The data verified the rationality and correctness of the simplified model of the contact finger. All in all this research has significance to the bus design and the temperature field of contact and contact finger.
    Key words: conract; contact finger; GIS bus; coupled field; contact resistance; temperature field
 
参考文献
[1] FUJINAMI H, TAKUMA T, KAWAMOTO T.Development of detection method with a magnetic field sensor forincomplete contact in gas-insulated switches and busconnecting parts[J].IEEE Transactions on Power Delivery,1995,10(1) :229-236.
[2] PURUSHOTHAMAN S, DE LEON F.Heat-transfer model for toroidal transformers[J].IEEE Transactions on Power Delivery,2012,27(2) :813-820.
[3] 黎斌.SF6 高压电器设计[M]. 北京:机械工业出版社,2015.
[4] 纽春萍,强若辰,荣命哲,等. 弹簧触指的稳态温升仿真与实验研究[J]. 高压电器,2015,51(3) :8-14.
[5] 冯慈璋,马西奎. 工程电磁场导论[M] . 北京:高等教育出版社,2000.
[6] 吴晓文,舒乃秋,李洪涛,等. 基于光纤光栅的气体绝缘开关母线温度在线监测系统[J] . 电力自动化设备,2013,33(4):155-160.
[7] 丁祖荣. 流体力学[M] . 北京:高等教育出版社,2003.
[8] 刘志刚,耿英三,王建华,等. 基于流场-温度场耦合计算的新型空心电抗器设计与分析[J] . 电工技术学报,2003,18(6):59-63.
[9] 路义萍,陈朋飞,邓海燕,等. 某新型通风方式空冷汽轮发电机转子三维温度场[J] . 电工技术学报,2010,25(11) :29-35.
[10] 赵镇南. 传热学[M]. 北京:高等教育出版社,2008.